SPECIFICATIONS
Conductor: Solid Bare Copper (1 x AWG23)
Insulation :
- HDPE
- Min. Avg. Thickness: 0.45 mm;
- Min. Thickness: 0.38 mm
Color Code:
- Pair 1: Blue & White
- Pair 2: Orange & White
- Pair 3: Green & White
- Pair 4: Brown & White
Shield: Aluminum-Mylar tape and Drain wire(tinned copper conductor)
Jacket:
- 75°C PVC Compound
- Min. Avg. Thickness: 0.585 mm;
- Min. Thickness: 0.458 mm
- Approximate O.D.: 7.8 mm +/- 0.3mm
Electric Requirements: (Cable length: 100M)
- Characteristic Impedance(Zo): 85~115Ω (1~500 MHz)
- DC. Resistance Capacitance Unbalance: 3%
- Pair-to-Ground Capacitance Unbalance: 330 pF/100M Max
- Conductor Resistance: 7.32Ω/ 100M 20°C Max
- Mutual Capacitance: 5600 pF/100m Max
Spark Test: Outer Jacket: 2.5KV Insulation: 1.75KV
Dielectric Strength: 1.5KV AC/2secs
- Nominal Velocity of Propagation (NVP): 74 %
Temperature Range:
- Installation Temperature 0 to 50°C
- Storage Temperature -20 to 70°C
- Operation Temperature -10 to 60°C